Measuring and Explaining Inrush Current
At 5:27 in
MASTER ELECTRICIAN DAD TEACHES SON HOW TO TROUBLESHOOT A 480 VOLT PANEL!
What happens here
The technician performs a live test using the clamp meter to demonstrate the "inrush current" that occurs when the circuit breaker is re-engaged. He initially takes a reading of 0.66 amps before starting a piece of equipment. When the equipment starts, the meter briefly surges to 256 amps before settling down to 32 amps. He explains that this high inrush current, while momentary, is the cause of the "buzzing" and could eventually damage the 100-amp circuit breaker, even though it's not enough to trip it due to its short duration. The problem was not the circuit breaker itself, but rather an issue with the load it was connected to, likely on the roof.
Goal: Quantify the inrush current and explain its impact on the circuit breaker.
Tools and materials
- 480-Volt Electrical Panel — The live electrical panel where current measurements are taken, Clamp Meter Unknown
What they say
(1,030 characters)Hide
What they say
(1,030 characters)Auto-generated from the video audio.